14ACX - 1.5 to 5 Ton Air Conditioner / Page 9
SOUND DATA
1
Unit
Model
Octave Band Linear Sound Power Levels dB, re 10
-12
Watts
Center Frequency - HZ
1
Sound Rating
Number (dB)
125
250
500
1000
2000
4000
8000
018
69.5
70.5
71.0
71.0
69.0
63.5
57.5
76
024
69.5
72.0
70.5
70.5
67.5
62.5
57.5
76
030
72.5
74.0
74.0
72.0
67.5
61.5
56.5
76
036
73.5
75.0
74.0
72.5
67.5
62.5
56.5
76
041
76.5
74.0
73.5
73.5
70.0
62.5
58.5
78
042
73.5
75.5
74.5
73.5
70.5
64.0
58.5
78
047
76.5
77.5
77.5
73.5
69.0
63.5
60.5
80
048
76.5
74.0
73.5
73.5
70.0
62.5
58.5
78
059
79.5
76.5
76.5
72.5
68.0
63.0
60.5
78
060
76.5
77.5
77.5
73.5
69.0
63.5
60.5
80
NOTE - the octave sound power data does not include tonal correction.
1
Tested according to AHRI Standard 270-2008 test conditions.
AHRI STANDARD 210/240
Cooling or heating capacities are net values, including
the effects of blower motor heat, and do not include
supplementary heat. Power input is the total power input
to the compressor(s) and fan(s), plus any controls and
other items required as part of the system for normal
operation.
Units which do not have an indoor air-circulating blower
furnished as part of the model, i.e., split system with
indoor coil only, is established by subtracting from the
total cooling capacity 1250 Btu/h per 1,000 cfm, and by
adding the same amount to the heating capacity. Total
power input for both heating and cooling is increased by
365 W per 1,000 cfm of indoor air circulated.
TXV USAGE
Use this table for C33, C35, CH23, CH33, CH35 and CR33
Field Installed TXV Match-Ups.
Outdoor Unit
Model No.
Thermal Expansion Valve
(TXV)
14ACX(-)(S)018
12J18
14ACX(-)(S)024
12J18
14ACX(-)(S)030
12J18
14ACX(-)(S)036
12J19
14ACX-041
12J20
14ACX(-)(S)042
12J20
14ACX-047
12J20
14ACX-048
12J20
14ACX-059
12J20
14ACX-060
12J20
CX34 and CX35 upflow coils and all Lennox air handlers are shipped with a
factory installed TXV. In most cases, no change out of the valve is needed.
If a change out is required it will be listed in the “TXV SUBSTITUTIONS” table.
The correct TXV must be ordered separately and field installed.
C33, C35 and CH33 and CH35 coils - Replace the factory installed orifice with
the expansion valve listed .
CR33 and CH23 coils - Use the expansion valve listed.
MOST POPULAR MATCHES
Outdoor Unit
Model No.
Indoor Unit
Model No
14ACX(-)(S)018
CX34-25
14ACX(-)(S)024
CX34-25
14ACX(-)(S)030
CX34-31
14ACX(-)(S)036
CX34-38
14ACX-041
CX34-49
14ACX(-)(S)042
CX34-49
14ACX-047
CX34-62C
14ACX-048
CX34-62C
14ACX-059
CX34-62C
14ACX-060
CX34-62C
*TXV SUBSTITUTIONS
Use this table to determine if the factory installed TXV in
the indoor unit needs to be replaced.
Outdoor Unit
Model No.
Indoor Coil
Factory
TXV
Replacement
TXV
14ACX(-)(S)030 CX34-42
12J20
12J18
14ACX(-)(S)030 CX34-43
12J20
12J18
14ACX(-)(S)030 CX35-48
12J20
12J18
14ACX(-)(S)036 CX34-31
12J18
12J19
* CX34 and CX35 coils - The factory installed expansion valve must be
replaced with the expansion valve listed (ordered separately).
If the combination is not listed above, the factory installed TXV is used.