RFC ORIFICE USAGE (NORTH/SOUTH REGIONS)
LEGEND:
◄ Green = Matches Orifice Furnished With Indoor Coil (no replacement necessary)
▲ Yellow = Matches Orifice Furnished With Outdoor Unit (orifice must be field replaced)
Blue = Field Provided (must be ordered extra for field replacement)
C33 COILS
Indoor Coil
Model No.
Factory
Orifice
Furnished
in Coil
Outdoor Unit Model No. - Orifice Furnished With Outdoor Unit
14ACXS018
14ACXS024
14ACXS030
14ACXS036
14ACXS042
0.053
0.060
0.067
0.071
0.083
C33-19A-2
0.051
0.060 ▲
C33-25A-2
0.057
0.053 ▲
0.060 ▲
0.067 ▲
C33-25B-2
0.057
0.053 ▲
0.060 ▲
0.067 ▲
C33-31A-2
0.065
0.053 ▲
0.060 ▲
0.067 ▲
0.071 ▲
C33-31B-2
0.065
0.053 ▲
0.060 ▲
0.067 ▲
0.071 ▲
C33-36A-2
0.073
0.060 ▲
C33-36B-2
0.073
0.060 ▲
C33-36C-2
0.073
0.060 ▲
C33-38A-2
0.073
0.060 ▲
0.067 ▲
0.071 ▲
C33-38B-2
0.073
0.060 ▲
0.067 ▲
0.071 ▲
C33-43B-2
0.076
0.067 ▲
0.071 ▲
C33-43C-2
0.076
0.067 ▲
0.071 ▲
C33-48B-2
0.082
0.071 ▲
C33-48C-2
0.082
0.071 ▲
C33-49C-2
0.082
0.071 ▲
0.083 ▲
C33-50/60C-2
0.082
0.071 ▲
C33-62C-2
0.093
0.083 ▲
C35 COILS
Indoor Coil
Model No.
Factory
Orifice
Furnished
in Coil
Outdoor Unit Model No. - Orifice Furnished With Outdoor Unit
14ACXS018
14ACXS024
14ACXS030
14ACXS036
14ACXS042
0.053
0.060
0.067
0.071
0.083
C35-18A/24-2F
0.053
◄ 0.053
C35-18/24B-2F
0.053
◄ 0.053
C35-24A-2F
0.057
0.053 ▲
◄ 0.057
0.063
C35-24B-2F
0.057
0.053 ▲
◄ 0.057
0.063
C35-30A-2F
0.067
0.057
◄ 0.067
0.071 ▲
C35-30B-2F
0.067
0.057
◄ 0.067
0.071 ▲
C35-30/36A-2F
0,057
◄ 0.057
C35-30/36B-2F
0,057
◄ 0.057
C35-30/36C-2F
0,057
◄ 0.057
C35-36A-2F
0.070
0.057
0.065
◄ 0.070
C35-36B-2F
0.070
0.057
0.065
◄ 0.070
C35-48B-2F
0.071
0.063
◄ 0.071
C35-48C-2F
0.071
0.063
◄ 0.071
C35-49C-2F
0.076
0.070
0.077
C35-50/60C-2F
0.070
◄ 0.070
C35-60D-2F
0.077
◄ 0.077