LNL-1100-20DI Input Control Module
64 —
revision 7
18
Specifications
The LNL-1100-20DI is intended for use in low voltage, Class 2 circuits only.
The following specifications are subject to change without notice.
•
Primary Power:
From the LNL-3300-M5; 12 VDC, ± 10 %, 165 mA maximum
•
Inputs:
20 unsupervised/supervised; Standard EOL: 1K/1K ohm, 1%, 1/4 watt
•
Communication:
9600, 19200, 38400, or 115200 bps, asynchronous
•
Alarm Input Cable Requirements:
1 twisted pair per input, 22 AWG shielded. 30 ohms maximum
loop resistance
•
Environmental:
-
Storage Temperature:
-67 to +185°F (-55 to +85°C)
-
Operating Temperature:
+32 to +158°F (0 to +70°C)
-
Humidity:
5 to 95% RHNC
•
Mechanical:
-
Width:
3.5 in. (88.9 mm)
-
Length:
10.25 in. (260.4 mm)
-
Height:
0.69 in. (17.5 mm)
-
Weight (without connectors):
4 oz (113 g) nominal
Summary of Contents for LNL-3300-M5
Page 1: ...7 3 M Series Installation Guide...
Page 4: ......
Page 9: ...HARDWARE INSTALLATION GUIDELINES...
Page 10: ......
Page 33: ...LNL 3300 M5 INTELLIGENT SYSTEM CONTROLLER...
Page 34: ......
Page 54: ...LNL 3300 M5 Intelligent System Controller 54 revision 7...
Page 55: ...LNL 1100 20DI INPUT CONTROL MODULE...
Page 56: ......
Page 65: ...LNL 1200 16DO OUTPUT CONTROL MODULE...
Page 66: ......
Page 75: ...LNL 1200 16DOR OUTPUT CONTROL MODULE...
Page 76: ......
Page 86: ...LNL 1200 16DOR Output Control Module 86 revision 7...
Page 87: ...LNL 1320 2RP DUAL DOOR CONTROL MODULE...
Page 88: ......
Page 108: ...LNL 1320 2RP Dual Door Control Module 108 revision 7...
Page 109: ...LNL 1320 S2RP DUAL DOOR CONTROL MODULE...
Page 110: ......
Page 131: ...LNL 1340 M2K FOUR READER INTERFACE MODULE...
Page 132: ......
Page 155: ...LNL 1380 8RP READER INTERFACE MODULE...
Page 156: ......
Page 170: ...LNL 1380 8RP Reader Interface Module 170 revision 7...
Page 171: ...LNL 8000 MCOM RS 485INTERFACE MODULE...
Page 172: ......
Page 178: ...LNL 8000 MCOM RS 485 Interface Module 178 revision 7...