M Series Installation Guide
revision 7 —
99
Unsupervised Input Wiring on F/2F Reader
31.2.3
Supervised Inputs wired to the F/2F Reader
Supervised inputs for the door position monitor and REX switches are wired directly to the F/2F reader
configured for 4-State Supervision: open, closed, short, and cut. See the reader’s documentation for the
proper connection terminals. EOL resistors typically require two 1K ohm resistors as shown in the figure
below. Install the EOL resistors as close to the switch as possible.
Unsupervised Input Wiring on F/2F Reader Callouts
Callout
Description
1
F/2F reader
2
To LNL-1320-2RP
3
+5 VDC/+12 VDC connection
4
Ground connection
5
Door DO (reader LED) connection
6
Data 1 connection
7
Normally Closed contact for door monitor switch
8
Normally Open contact for Request-to-Exit (REX) switch
1
2
3
4
5
6
7
8
Summary of Contents for LNL-3300-M5
Page 1: ...7 3 M Series Installation Guide...
Page 4: ......
Page 9: ...HARDWARE INSTALLATION GUIDELINES...
Page 10: ......
Page 33: ...LNL 3300 M5 INTELLIGENT SYSTEM CONTROLLER...
Page 34: ......
Page 54: ...LNL 3300 M5 Intelligent System Controller 54 revision 7...
Page 55: ...LNL 1100 20DI INPUT CONTROL MODULE...
Page 56: ......
Page 65: ...LNL 1200 16DO OUTPUT CONTROL MODULE...
Page 66: ......
Page 75: ...LNL 1200 16DOR OUTPUT CONTROL MODULE...
Page 76: ......
Page 86: ...LNL 1200 16DOR Output Control Module 86 revision 7...
Page 87: ...LNL 1320 2RP DUAL DOOR CONTROL MODULE...
Page 88: ......
Page 108: ...LNL 1320 2RP Dual Door Control Module 108 revision 7...
Page 109: ...LNL 1320 S2RP DUAL DOOR CONTROL MODULE...
Page 110: ......
Page 131: ...LNL 1340 M2K FOUR READER INTERFACE MODULE...
Page 132: ......
Page 155: ...LNL 1380 8RP READER INTERFACE MODULE...
Page 156: ......
Page 170: ...LNL 1380 8RP Reader Interface Module 170 revision 7...
Page 171: ...LNL 8000 MCOM RS 485INTERFACE MODULE...
Page 172: ......
Page 178: ...LNL 8000 MCOM RS 485 Interface Module 178 revision 7...