![Lauda Viscotemp 15 G Operation Manual Download Page 110](http://html1.mh-extra.com/html/lauda/viscotemp-15-g/viscotemp-15-g_operation-manual_4122547110.webp)
110 / 134
ECO Gold
18.2.2
Procedure for setting the control parameters for external control
1.
Activating external control (
2.
Set the slave controller:
2.1.
Parameter to
auto
;
Xpf in dependence of:
Check or adjust device type (
Select heat transfer liquid with as low-viscosity and with as high a thermal capacity as possible.
Ranking list: Water, water/glycol, oils, Fluorinert®.
Set pump level as high as possible,
Make sure there is adequate circulation,
select the hose length as short as possible, e.g. 2 x 1 m,
select the hose cross-sectional area as large as possible, e.g. ½ inch,
set the throughput through the external consumer as large as possible.
2.2.
Set Xpf:
With a tendency to oscillate with a short period of oscillation (e.g. 30 s)
Xpf smaller, otherwise larger,
with poor thermal coupling and a large mass to temper
large (e.g. 2 – 5, possibly even larger),
with good thermal coupling and a small mass to temper
small (e.g. 0.2 – 0.7),
if fast temperature changes are required, external baths should be controlled if possible with internal control. Other-
wise choose Xpf to be very small (0.05 – 0.1).
3.
Setting the master controller (PID controller):
First start with Auto, then possibly continue with manual.
3.1.
Setting Kpe:
With a tendency to oscillate (long period of oscillation, e.g. 10 min)
Kpe larger, otherwise smaller,
3.2.
Setting Tne/ Tve/ Tde:
Generally quite high values (Tne = 70 s – 200 s; Tve = 50 s – 150 s),
with smaller values
faster transient responses, otherwise slower transient responses and therefore less oscillation,
Tve: To reduce transients
increase Tve, otherwise vice versa,
Tde (damping for Tve): generally approx. 10 % of Tve.
4.
Correcting quantity limit (
18.2.1) and temperature limits (Til/Tih) (
Set according to the physical boundary conditions.
Example:
Heat transfer liquid
Correcting quantity limit
Til
Tih
Water
depends on heat transfer liquid and vessel
5 °C
95 °C
Summary of Contents for Viscotemp 15 G
Page 77: ...11 Declaration of Conformity 09 2021 ECO Gold 77 134 ...
Page 78: ...78 134 ECO Gold 09 2021 ...
Page 81: ...09 2021 ECO Gold 81 134 W Warnings 53 92 X Xp 106 Xpf 108 ...
Page 82: ...82 134 ECO Gold 09 2021 ...
Page 83: ...09 2021 ECO Gold 83 134 ...
Page 84: ...84 134 ECO Gold 09 2021 ...
Page 85: ...09 2021 ECO Gold 85 134 Appendix with settings ...
Page 121: ...09 2021 ECO Gold 121 134 Click on the tab with the mouse and then on the Device manager ...
Page 129: ...09 2021 ECO Gold 129 134 ...
Page 130: ...130 134 ECO Gold 09 2021 ...
Page 131: ......