Table 9-32 Modbus Configuration
Note:
The serial line protocol must also be configured for Modbus, in addition to
configuring the Modbus server. See
and
for
details.
To View and Configure the Modbus Server
Using Web Manager
To view Modbus statistics, on the
Administration
page, click
Modbus
>
Statistics
.
To configure Modbus settings, on the
Administration
page, click
Modbus
>
Configuration
.
Using the CLI
To enter the Modbus command level:
enable > configure > modbus
Using XML
Include in your file:
<configgroup name=”modbus">
RSS
An RDF Site Summary (RSS) syndication feed is served by the HTTP Server. This feed contains
up-to-date information regarding the configuration changes that occur on the SGX 5150 gateway.
Specifying the RSS Feed to be Persistent results in the data being stored on the filesystem. The
file used is
/cfg_log.txt
. This allows feed data to be available across reboots (or until the
factory defaults are set).
Each RSS Feed entry contains a standard timestamp in its
<pubDate>
field.
The RSS Feed is a scrolling feed in that only the last Max Entries entries are cached and viewable.
Simply register the RSS Feed within your favorite RSS aggregator and you will automatically be
notified of any configuration changes that occur.
Table 9-33 RSS
Modbus Configuration
Settings
Description
TCP Server State
Select
On
or
Off
. If
On
, the Modbus server is active on TCP 502.
Additional TCP Server Port
Enter the Additional TCP Server Port, if any.
Note:
If present, is used in addition to TCP port 502.
Response Timeout
Enter the number of milliseconds to wait for a response on the serial side.
The SGX 5150 gateway returns exception code 11 to the network master
controller if the slave serial device fails to reply within this time out.
RSS Trace Input
Enable or disable the
RSS Trace Input
by clicking
On
or
Off
.
RSS Settings
Description
RSS Feed
Click to select whether to turn the RSS Feed
On
or
Off
.