77
16.7 Stop-function connection
The TSG electronics has a stop function, which can be designed as single-channel or dual-channel. During
normal operation and without using the stop function, there is a wire bridge between X5.1 and X5.2.
Table 37: Stop-function X5
Connection of the stop function X5:
X5.1
Potential-free contact
0[Vdc] – 24[Vdc] / 10mA
X5.2
Potential-free contact
Table 38: Control voltage connection - Connection data
Connection of the stop function X5 (2-pole PCB terminal):
Conductor cross-section rigid/flexible (min./max.)
(Stripping length: 5[mm])
0,5 /1,5 [mm²]
Flexible conductor cross-section with wire end ferrule with/without plastic
sleeve (min./max.)
0,5 / 1,5 [mm²]
Wire gauge AWG (min./max.)
20…15
Use 60[°C] copper conductors only.
CAUTION:
No external voltage may be connected to terminals X5.1 and/or X5.2. This leads to irreparable
damage to the TSG electronics and can lead to unintentional door movements!