5 Electrical settings and commissioning
5.1 Display
The TSG electronics unit has a two-digit 7-segment display to indicate the current state and show the menu
with parameters and their corresponding values.
Table 1: TSG display
Display
Meaning
There is no activation present.
The TSG self learn procedure has not been carried out.
Open signal is present (
Op
en).
Close signal is present (
Cl
ose).
Door is opened (
O
pene
d
).
Door is closed (
C
lose
d
).
Door is
Obstructed
.
NOTE:
Note! If the display is not used for 10 minutes or more, the display switches itself off
automatically. By turning or pressing the jog wheel, the display is switched on again.