8 TSG connections
8.1 X1 inputs
The inputs for signals "Open door" (X1.1), "Close door" (X1.2) and (reserved) (X1.3) can be wired with a
voltage of 24 [VDC/AC] (see also Table 13: X1 inputs / page 44).
CAUTION:
All inputs have a common potential, which means that the
same voltage
must always be
applied to all three inputs!
If alternating voltage (AC) is applied, only one phase will be applied. Different phases must
not be applied! Doing so may cause damage to the electronics components!
8.2 X2 outputs
There are three relay outputs on the TSG electronics unit to display or report door status, each with a
changeover contact that has contacts terminated on the X2 terminal strip (see also Table 14: X2 - relay
outputs / page 45).
Message
Contacts
"Door is Open"
X2.1/2/3
"Door is Closed"
X2.4/5/6
"Door is Obstructed"
X2.7/8/9