Select ON only if a safety sensor has been installed on opening.
We recommend that you adjust the safety sensor detection field before starting the set-up, to
allow the operator to precisely store the position of any side wall.
Only if S05 function has been set to ON
Select ON if a safety sensor has been installed on closing and monitored (as required by
standard EN 16005) to activate sensor test at the beginning of each cycle, select OFF only if
the safety sensor on closing has not been set up to be monitored.
For more information, refer to "Safety sensors" paragraph.
Only if S06 function has been set to ON
Select ON if a safety sensor has been installed on opening and monitored (as required by
standard EN 16005) to activate sensor test at the beginning of each cycle, select OFF only if
the safety sensor on closing has not been set up to be monitored.
For more information, refer to "Safety sensors" paragraph.
If S07 and/or S08 functions are set to ON only
Select test logic status, used by operator control unit to monitor safety sensors.
The set-up depends on the characteristics of sensor installed.
Select OFF when using “4SAFE ON SW” or "OA-EDGET" type sensors;
select ON when using “TOP SCAN-S” type sensors.
For more information, refer to "Safety sensors" paragraph.
Contact configuration on OPEN input between terminals 6-7 of PWN-T board.
Select ON with normally open contact or when the OPEN input is not used.
Select OFF when using a device with normally closed contact.
The operator is ready for the set-up cycle.
Exit the detection field of the opening safety sensor during the set-up, to allow the sensor to
only detect the presence of any side wall at the end of the opening.
Press the (OK) button
The control unit buzzer emits 4 beeps and starts the opening cycle at slow speed.
When the opening stroke is completed, a long beep indicates that the set-up has been
successful.
The door automatically closes again.
25