OFF
Opening safety sensor input deactivated; if a opening safety sensor is not installed
ON
Opening safety sensor input activated; if a opening safety sensor is installed
OFF
Test on closure safety sensor deactivated. For sensors without monitoring function carried out by the
automation control unit
OFF
Test on opening safety sensor deactivated. For sensors without monitoring function carried out by the
automation control unit
OFF
Active function if
F20
or
F21=ON
. Safety sensor test with LOW logic level.
For detailed information please check paragraph "Safety Sensors Device"
ON
Active function if
F20
or
F21=ON
. Safety sensor test with HIGH logic level.
For detailed information please check paragraph "Safety Sensors Device"
F23
Function disabled
F24
OPEN input is not enabled in the “Free manual door” work program.
OFF
Constant pause time
ON
Automatic pause time increases if door is not closing properly due to the high flow of persons walking
through it
OFF
Interlock function deactivated
ON
Interlock function activated. Please check paragraph "Interlock System"
OFF
Active function if
F26=ON
. Delayed door opening for 0,5" after opening command.
Please check paragraph "Interlock System"
ON
Active function if
F26=ON
. Prompt door opening at opening command.
Please check paragraph "Interlock System"
OFF
Active function if
F26=ON
. Opening command is not being saved.
Please check paragraph "Interlock System"
ON
Active function if
F26=ON
. Opening command is being saved.
Please check paragraph "Interlock System"
OFF
OPEN input configuration; normally closed contact. When a device with N.C. contact is installed
ON
OPEN input configuration; normally open contact. When a device with N.O. contact is installed
OFF
For double leaf application: in case of power failure the two leaves starts simultaneously in the first opening
phase
ON
For double leaf application: in case of power failure the two leaves starts respecting the offset in the first
opening phase
S
S
S
S
F19
F22
F25
F26
F27
F28
Active function if
F18=ON
. Test on closure safety sensor activated. For sensors with monitoring function
carried out by the automation control unit (cat. 2 / pl. c). For detailed information please check paragraph
"Safety Sensors Device"
ON
F20
F21
ON
Active function if
F19=ON
.Test on opening safety sensor activated. For sensors with monitoring function
carried out by the automation control unit (cat. 2 / pl. c). For detailed information please check paragraph
"Safety Sensors Device"
F29
F30
F31
FUNCTION STATUS
DESCRIPTION
*' SLAVE
33
OFF
ON
OPEN input is enabled also in the “Free manual door” work program in order to allow the automatic opening
of the door.
KEEP IN OFF