Page 91
106
Flame lost in MFEP
L
1. Check main valve wiring and operation -
correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown
tests.
4. Check ignition transformer electrode, fl ame
detector, fl ame detector siting or fl ame rod
position.
5. If steps 1 through 4 are correct and the fault
persists, replace the module.
107
Flame lost early in run
L
108
Flame lost in run
L
109
Ignition failed
L
110
Ignition failure occurred
H
Hold time of recycle and hold option. Will not
be a lockout fault. Hold Only. Internal hardware
test. Not a lockout.
111
Flame current lower than weak
threshold (min fl ame current
0.8mA).
H
Hold time of recycle and hold option. Will not
be a lockout fault. Hold Only. Internal hardware
test. Not a lockout.
113
Flame circuit timeout
L
Flame sensed during Initiate or off cycle, hold
240 seconds, if present after 240 seconds,
system will lockout.
119
Control Interaction Fault
H
Flap valve identifi cations confi gured incorrectly.
122
Lightoff rate proving failed
L
1. Check wiring and correct any potential wiring
errors.
2. Check the VFDs (Variable-speed Fan Drive)
ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
123
Purge rate proving failed
L
128
Fan speed failed during prepurge
H or L
129
Fan speed failed during
preignition
H or L
130
Fan speed failed during ignition
H or L
131
Fan movement detected during
standby
H
132
Fan speed failed during run
H
137
ILK (Interlock) failed to close
H
1. Check wiring and correct any possible
shorts.
2. Check Interlock (ILK) switches to assure
proper function.
3. Verify voltage through the interlock string to
the interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
149
Flame detected
H or L
Holds if fl ame detected during Safe Start check
up to Flame Establishing period.
150
Flame not detected
H
Sequence returns to standby and restarts
sequence at the beginning of Purge after the
HF switch opens if fl ame detected during Safe
Start check up to Flame Establishing period.
154
Purge Fan switch On
H or L
1. Purge fan switch is on when it should be off.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3
and its connections. Make sure the switch
is working correctly and is not jumpered or
welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.
Code
Description
Lockout
or Hold
Procedure
N
EO
T
HERM
Commercial Boilers and Water Heaters
Summary of Contents for Neotherm NTH
Page 4: ...LAARS Heating Systems...
Page 36: ...Page 36 Figure 22 Hydronic Piping Single Boiler Zoning with Circulators LAARS Heating Systems...
Page 52: ...Page 52 Figure 36 Ladder Diagram 7 H Ladder Diagram LAARS Heating Systems...
Page 100: ...Page 100 Parts Illustration 4 Internal Components Sizes 750 850 LAARS Heating Systems...
Page 102: ...Page 102 Parts Illustration 6 Gas Train Components Sizes 600 850 LAARS Heating Systems...