Page 87
16
Internal fault:
Safety relay test failed due to
safety relay OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
17
Internal fault:
Safety relay test failed due to
safety relay not OFF
L
18
Internal fault:
Safety relay test failed due to
feedback not ON
L
19
Internal fault:
Safety RAM write
L
20
Internal fault:
Internal fault: Flame ripple and
overfl ow
H
21
Internal fault:
Flame number of sample
mismatch
H
22
Internal fault:
Flame bias out of range
H
23
Internal fault:
Bias changed since heating cycle
starts
H
24
Internal fault:
Spark voltage stuck low or high
H
25
Internal fault:
Spark voltage changed too much
during fl ame sensing time
H
26
Internal fault:
Static fl ame ripple
H
27
Internal fault:
Flame rod shorted to ground
detected
H
28
Internal fault:
A/D linearity test fails
H
29
Internal fault:
Flame bias cannot be set in
range
H
30
Internal fault:
Flame bias shorted to adjacent
pin
H
31
Internal fault:
SLO electronics unknown error
H
32-
46
Internal fault:
Safety Key 0 through 14
L
47
Flame Rod to ground leakage
H
48
Static fl ame (not fl ickering)
H
Code
Description
Lockout
or Hold
Procedure
N
EO
T
HERM
Commercial Boilers and Water Heaters
Summary of Contents for Neotherm NTH
Page 4: ...LAARS Heating Systems...
Page 36: ...Page 36 Figure 22 Hydronic Piping Single Boiler Zoning with Circulators LAARS Heating Systems...
Page 52: ...Page 52 Figure 36 Ladder Diagram 7 H Ladder Diagram LAARS Heating Systems...
Page 100: ...Page 100 Parts Illustration 4 Internal Components Sizes 750 850 LAARS Heating Systems...
Page 102: ...Page 102 Parts Illustration 6 Gas Train Components Sizes 600 850 LAARS Heating Systems...