KW Aufzugstechnik GmbH OPERATING MANUAL DAVID-613
DAVID-D613-V125-E 13.04.2021
Page - 235 -
Enter value and change OFF, 2 to 500 cm; Can be
changed later - possible in inspection mode or re-
turn to safe condition
Vnenn: 1,6 m/s -> 300 cm
Vnenn: 2,0 m/s -> 350 cm
Vnenn: 2,5 m/s -> 400 cm
ANTSsafe
Delay Contro Top has been saved!
Note:
(setup-3 means that all ASA parameters
have been configured but no floors have been
learned into the ASA)
Note:
If DSK is active, i. the floors have already
been taught-in in the D613 and the flush levels are
set then: ENTER ->STEP-3 key otherwise:
DOWN
key
3.8 STEP-2: D613-Learn leves and adjust levels
Two methods can be selected
for learning floors
, in the
B43 menu learning floors:
Summary of Contents for DAVID 613
Page 1: ...OPERATING MANUAL LIFT CONTROLLER SYSTEM DAVID 613 FUNCTIONS START UP INSTRUCTIONS...
Page 2: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 2...
Page 10: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 10...
Page 12: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 12...
Page 13: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 13...
Page 14: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 14...
Page 34: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 34...
Page 35: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 35...
Page 98: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 98...