![Kurz 410FTB Operation Manual Download Page 99](http://html1.mh-extra.com/html/kurz/410ftb/410ftb_operation-manual_2011415099.webp)
Kurz
B
‐
Series
Operations
Guide
4–26
Program Mode
Advanced Setup
Option 11 — Setting Up a Pulse Output
When
a
relay
is
configured
to
the
Pulsed
Output
of
Totalized
Flow
from
the
Setup
Relay
Outputs
Menu
(option
8),
the
meter
advances
to
the
Setup
Pulsed
Output
menu.
Note
The
relays
are
rated
for
0.5A.
To
access
the
Pulse
Output
menu
in
Program
mode:
1>
Press
P
.
2>
Enter
the
Advanced
access
code,
and
then
press
E
.
3>
Press
2
to
invoke
the
Quick
Jump
option.
4>
Press
11
for
the
Pulse
Output
menu,
and
then
press
E
.
The
message
“Pulse
output
is
not
installed”
if
the
meter
was
not
purchased
with
the
pulse
output
option.
If
the
option
is
installed,
the
following
prompt
appears:
PULSE OUTPUT
>ON ^v
You
are
prompted
to
set
the
Totalizer
Pulse
Output
function
ON
or
OFF.
5>
Use
the
arrow keys
to
select
ON,
and
then
press
E
.
PULSE OUTPUT #1
ASSIGNED TO DO1
A
prompt
confirming
the
relay
assignment
appears.
6>
Press
E
or
P
to
continue.
SCF PER PULSE
>100000.000
A
prompt
for
the
Totalized
Flow
Per
Pulse
appears.
This
value
defines
the
accumulated
flow
per
pulse,
which
are
the
units
of
volume
or
mass
per
pulse
based
on
the
system
units.
(The
example
uses
English
and
standard
cubic
feet.)
7>
Enter
the
value
using
the
number
and
decimal
keys,
and
then
press
E
.
PULSE WIDTH
>50 MSEC
A
prompt
for
the
Pulse
Width
appears.
This
is
the
length
of
time
to
close
the
assigned
relay
after
reaching
the
accumulated
volume
or
mass.
The
pulse
width
can
be
set
from
50
to
2000
msec.
8>
Enter
the
number
of
milliseconds
using
the
number
keys,
and
then
press
E
.
Press
P
if
you
want
to
skip
entering
a
value.
Summary of Contents for 410FTB
Page 1: ...Operations Guide for B Series Flow Meters 368042E...
Page 4: ...Kurz B Series Operations Guide iv...
Page 9: ...Kurz B Series Operations Guide ix Preface...
Page 33: ...Kurz B Series Operations Guide 1 20 B Series Flow Meter Modes Menus...
Page 65: ...Kurz B Series Operations Guide 2 32 B Series Flow Meter Display Mode Options...
Page 141: ...Kurz B Series Operations Guide 4 68 Program Mode Advanced Setup...