1.1.2
Parameterization of Motor data
A PumpDrive 2 is parameterized for a 2 pole SuPremE Motor. The pump rotation is clockwise.
Name plate of motors:
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-2-1-1
Nominal Motor Power
0.55 [kW]
Preset: 0.55 [kW]
ServiceTool, Display
3-2-1-2
Nominal Motor Voltage
374 [V]
Preset: 400 [V]
ServiceTool, Display
3-2-1-3
Nominal Motor Frequency
50.0 [Hz]
Preset: 50.0 [Hz]
ServiceTool, Display
3-2-1-4
Nominal Motor Current
1.60 [A]
Preset: 1.60 [A]
ServiceTool, Display
3-2-1-5
Nominal Motor Speed
1500 [1/min]
Preset: 1500 [1/min]
ServiceTool, Display
3-2-1-6
Nominal Cos Phi Value
0.67
Preset: 0.57
ServiceTool, Display
3-2-2-1
Minimum Motor Speed
500 [1/min]
Preset: 500 [1/min]
ServiceTool, Display
3-2-2-2
Maximum Motor Speed
1500 [1/min]
Preset: 1500 [1/min]
ServiceTool, Display
3-2-3-1
PTC Data Analysis
1 = ON
Preset: ON
ServiceTool, Display
3-2-3-2
Thermal Motor Protection Be-
haviour
Non-self-acknowledging
Preset: Non-self-acknowledg-
ing
ServiceTool
3-2-4
Motor Direction of Rotation
0 = Clockwise
4)
Preset: Clockwise
ServiceTool, Display
3-3-1
Motor Control Method
Vector SuPremE
Preset: SuPremE Vector Con-
trol
ServiceTool
3-3-4-1
Update Motor Parameters
Run
Preset
ServiceTool
2) Pre-settings for completely assembled pump, motor, drive
4) Pump dependent