3.2.2
Closed loop control redundant: differential pressure with PumpMeter (Modbus)
Etaline Z double pump (2x100%): A constant differential pressure of 4 bar is needed. PumpMeter is used as a differential pressure sensor
in the measurement range of -1 … 10 bar. PumpMeter is connected by Modbus to the M12 Module of the drive. The sensor signal of
PumpMeter is linked by a cross link cable (see accessories) from drive to drive. The AuxMaster can take over control if the Master fails.
The set point is given by the display. Pump changeover will take place regularly after 24 hours of operation.
D
C
Δp
2
5
Configuration of drive 1 (Master):
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-6-1
Type of Control
3 = Differential Pressure
preset
ServiceTool, Display
3-11-2-1
Minimum Pressure
-1.00 [bar]
Preset
ServiceTool
3-11-2-2
Maximum Pressure
10.00 [bar]
Preset
ServiceTool
3-11-2-3
Pressure Unit
bar
Preset
ServiceTool
1-3-2
Setpoint (Closed-loop Control)
4.00 [bar]
Acc. specified Q,H preset
ServiceTool, Display
3-8-4-1
Function M12 Module Input A
1 = PMtr Suction/Dis-
charge Pressure
Preset
ServiceTool, Display
3-13-5
PumpMeter Master/Slave
Master
Preset for Etaline Z
ServiceTool
3-7-1
Role in multi pump operation
0 = Master
Preset
ServiceTool, Display
3-7-2
Pumps running
1
Preset
ServiceTool, Display
3-7-4-1
Automatic pump change
1 = Operating hours
Preset
ServiceTool, Display
3-7-4-2
Time pump running
24
Preset
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
Preset
ServiceTool
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI
1)
18
Alarm
4
Actual value: tailor-made bus cable for the connection of PumpMeter to
the M12 Module (color: black, female: straight, male: angled)
5
Tailor-made bus cable for double and multi pump operation (color: pur-
ple, male: angled, male: angled)
6
Actual value: tailor-made cross link bus cable for the redundant connec-
tion of PumpMeter (color: black, female: angled, male: angled)
Nr.
Function
70
M12 Module: Double and multi pump operation
80
M12 Module: PumpMeter
A
M12 Module female A: connection PumpMeter (Modbus)
B
M12 Module female B: cross link bus cable PumpMeter (Modbus)
C
M12 Module female C: Bus resistor
D
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
PDrv2 Eco
Or local
Or PLC
Drive
Master
Aux Master
Modbus
Master!
Special Firmware Modbus
Master in PumpMeter is
needed. In case of Eta-
line Z the special firm-
ware is programmed in
factory
Drive 1 (Master)
Drive 2 (Aux Master)