Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 10 of 48
16
17
18
+24V
DI
18
DO
GND
16
17
16
17
GND
2
2
AO: 4...20mA
4...20mA
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
DO
11
0V (GND)
AO: OUT 0V(GND)
15
AIN
GND
11
14,85 mA
2000 1/min
2
2.1.3
Open loop control: control value by external signal 4…20mA
A fixed speed of 2000 1/min should be given by an external signal 4…20mA at analog input 1.
The feedback of the speed should be send by analog output to a PLC.
2000 1/min is equal to 14,85 mA when using a 2-pole motor with a nominal speed of 2950 1/min (16mA / 2950 rpm * 2000 rpm + 4 mA
= 14,85 mA). Information: the set point can’t be lower than the minimum speed
Nr.
Parameter
Change value to
Pre-settings by fac-
tory
2)
Changeable by
3-6-1
Type of Control
0 = OFF (Open-loop Control)
preset
ServiceTool, Display
3-2-2-1
Minimum Motor Speed
500 [1/min]
preset
ServiceTool, Display
3-2-2-2
Maximum Motor Speed
2950 [1/min]
preset
ServiceTool, Display
3-8-1-1
Analog Input 1 Signal
1 = 4…20mA
0 = Off
ServiceTool, Display
3-8-1-2
Analog Input 1 Function
1 = Setpoint/Control value
(Auto)
0 = No Function
ServiceTool, Display
3-8-1-3
Analog Input 1 Lower Limit
0 [1/min]
-
ServiceTool, Display
3-8-1-4
Analog Input 1 Upper Limit
2950 [1/min]
-
ServiceTool, Display
3-8-7-1
Assignment 1 Analog Output 1
Motor speed
preset
ServiceTool
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI1
1)
15
Analog output: speed
2
Set point (open loop): external signal4...20mA
18
Alarm
PDrv2 Eco
Or local
Or PLC
drive