Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 24 of 48
70
80
D
C
B
A
5
16
17
DO
GND
DO
11
16
17
11
16
17
GND
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
18
+24V
DI
18
11
3.
Double pump
3.1
Double pump – Open loop control
3.1.1
Open loop control: control value at display
Etaline Z double pump (2x100%): A fixed speed of 2000 1/min should be set on the display. The nominal speed of the 2 pole motor is
2950 1/min. Pump changeover will take place regularly after 24 hours of operation.
Configuration of drive 1:
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-6-1
Type of Control
0 = OFF (Open-loop Control)
preset
ServiceTool, Display
3-2-2-1
Minimum Motor Speed
500 [1/min]
preset
ServiceTool, Display
3-2-2-2
Maximum Motor Speed
2950 [1/min]
preset
ServiceTool, Display
1-3-3
Control Value (Open-loop Control)
2000 [1/min]
motor specific
ServiceTool, Display
3-7-1
Role in multi pump operation
0 = Master
preset
ServiceTool, Display
3-7-2
Pumps running
1
preset
ServiceTool, Display
3-7-4-1
Automatic pump change
1 = operating hours
preset
ServiceTool, Display
3-7-4-2
Time pump running
24 [h]
preset
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI
1)
18
Alarm
5
Tailor-made bus cable for double and multi pump operation (color:
purple, male: angled, male: angled)
Nr.
Function
70
M12 Module: Double and multi pump operation
80
M12 Module: PumpMeter
A
-
B
-
C
M12 Module female C: Bus resistor
D
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
PDrv2 Eco
Or local
Or PLC
Drive
Drive 1
Drive 2