Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 34 of 48
72
82
A
B
C
D
5
4
26
27
DO
GND
26
27
DO
11
11
26
27
GND
2
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
28
+24V
DI
28
Configuration Drive 2 (AuxMaster 1):
Nr.
Parameter
Change value to
Pre-settings by factory
2)
3-6-1
Type of Control
1= Discharge Pressure
3 = Differential pressure
3-11-2-1
Minimum Pressure
0.00 [bar]
-1.00 [bar]
3-11-2-2
Maximum Pressure
6.00 [bar]
6.00 [bar]
3-11-2-3
Pressure Unit
bar
Preset
1-3-2
Setpoint (Closed-loop Control)
4.00 [bar]
0,00 [bar]
3-8-2-1
Analog Input 2 Signal
2 = 2…10V
3)
0 = OFF
3-8-2-2
Analog Input 2 Function
5 = Discharge Pressure
0 = No Function
3-8-2-3
Analog Input 2 Lower Limit
0.00 [bar]
-
3-8-2-4
Analog Input 2 Upper Limit
6.00 [bar]
-
3-8-4-1
Function M12 Module Input A
2 = PMtr Internal Suction/Dis-
charge Pressure
4)
1 = PMtr Suction/Discharge Pressure
3-7-1
Role in Multiple Pump System
0 = Master control
Preset
3-7-2
Maximum Number of Pumps Running
1
1
3-7-4-1
Automatic Pump Changeover
1 = Runtime
Preset
3-7-4-2
Runtime Prior to Pump Changeover
24
Preset
3-8-6-1
Digital Input 1 Function
System Start
1)
Preset
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
3) On all drives will be the 4…20mA signal converted to 2…10V signal, if the DIP switch in the Master is set to „ON“
4) If PumpMeter is only used as an internal measured variable at input A of the M12 module (via Modbus) and not for control, the Func-
tion M12 Module Input A parameter (3-8-4-1) must be set to PMtr Internal Suction/Discharge Pressure.
Nr.
Function
26
Enable power electronic
27
Ground for digital inputs
11
System start with DI
1)
2
Actual value: pressure sensor 4…20mA
28
Alarm
4
Tailor-made bus cable for the connection of PumpMeter to the M12
Module (color: black, female: straight, male: angled)
5
Tailor-made bus cable for double and multi pump operation (color:
purple, male: angled, male: angled)
Nr.
Function
72
M12 Module: Double and multi pump operation
82
M12 Module: PumpMeter
A
M12 12 Module female A: connection PumpMeter (Modbus)
B
-
C
M12 Module female C: for Double and multi pump operation (KSB-de-
vice bus)
D
M12 Module female D: Bus resistor
O
N
AuxMaster 2
Oder vor Ort
Oder SPS
Im Gerät
O