Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 3 of 48
1.
Pre-Conditions
-
The motor data are set according to the operating manual.
-
The motor control is correct selected and suits to the motor.
-
The pump curves are stored in the drive.
Pre-settings from production
Pumps with PumpDrive are delivered with the following pre-settings:
Motor data
Motion control according to motor type
Pre-setting of PumpMeter including sensors
Pump curves
Type series
Etaline / Etaline Z
Etanorm, Etabloc, Etachrom
Multitec, Movitec, Sewatec
Retrofit Drive
PumpDrive spare part
selection
EasySelect
EasySelect
EasySelect
Material number
Motor data
preset
preset
Preset
-
Asynchronous motor
Vector ASM
Vector ASM
Vector ASM
-
SuPremE
Vector SuPremE
Vector SuPremE
Vector SuPremE
Vector SuPremE
with PumpMeter
Closed loop control: Differen-
tial pressure and sensors pre-
set
Closed loop control: pressure p
constant and sensors preset
-
-
without PumpMeter
Open-loop Control
Open-loop Control
Open-loop Control Open-loop Control
Pump curve
preset
preset
-
-
Setpoint
with PumpMeter: preset
with PumpMeter: preset
-
-
Retrofit PumpDrives, which will be selected in EasySelect, will be delivered only with motor data (work is in progress). The pump curves
must be parameterized on site, can be uploaded from PumpMeter, can be set from ServiceTool or display.
PumpDrives (spare parts), which are ordered by material numbers are not parameterized in the production.
Using a 0/4…20mA or 0/2…10V Sensor for control a PumpMeter can be used as internal sensor in parallel. PumpMeter used as internal
sensor improves the flow estimation.