Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 37 of 48
72
82
A
B
C
D
5
4
26
27
DO
GND
26
27
DO
11
11
26
27
GND
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
28
+24V
DI
28
Configuration Drive 2 (AuxMaster 1):
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Adjustable via
3-7-1
Role in Multiple Pump System
0 = Master control
Preset
ServiceTool, HMI
3-7-2
Maximum Number of Pumps Running
1
1
ServiceTool, HMI
3-7-4-1
Automatic Pump Changeover
1 = Runtime
Preset
ServiceTool, HMI
3-7-4-2
Runtime Prior to Pump Changeover
24
Preset
ServiceTool, HMI
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
3) On all drives will be the 4…20mA signal converted to 2…10V signal, if the DIP switch in the Master is set to „ON“
4) If there is a cross link cable for the redundant connection of the pressure sensor, only one switch CURR-IN should be set to ON. So the
4…20mA signal will be converted to 2…10V signal.
5) If an additional sensor is connected to the AUX master the DIP switch should be ON.
DIP Switch M12 Module Drive 2
Nr.
Function
26
Enable power electronic
27
Ground for digital inputs
11
System start with DI
1)
28
Alarm
4
Tailor-made cable for the connection of pressure sensor to the M12
Module
5
Tailor-made bus cable for double and multi pump operation (color:
purple, male: angled, male: angled)
6
tailor-made cross link bus cable for the redundant connection of the
pressure sensor (color: black, female: angled, male: angled)
Nr.
Function
72
M12 Module: Double and multi pump operation
82
M12 Module: PumpMeter / Pressure Sensor
A
M12 Module female A: connection pressure sensor
B
-
C
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
D
M12 Module female C: Bus resistor
AuxMaster 2
Oder vor Ort
Oder SPS
Im Gerät