Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 11 of 48
16
17
18
+24V
DI
18
DO
GND
16
17
16
17
GND
DO
DO
12
13
12
13
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
DO
11
11
2.1.4
Open loop control: digital motor potentiometer
A fixed speed of 2000 1/min should be changeable by the digital inputs with an increment of 10 [1/min].
13
12
+/- 2000 1/min
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-6-1
Type of Control
0 = OFF (Open-loop Control)
preset
ServiceTool, Display
3-2-2-1
Minimum Motor Speed
500 [1/min]
preset
ServiceTool, Display
3-2-2-2
Maximum Motor Speed
2950 [1/min]
preset
ServiceTool, Display
1-3-3
Control Value (Open-loop Control)
2000 [1/min]
motor specific
ServiceTool, Display
3-8-6-2
Digital Input 2 Function
Potentiometer Auto -
No Function
ServiceTool
3-8-6-3
Digital Input 3 Function
Potentiometer Auto +
No Function
ServiceTool
3-6-6-2
Speed Change Increment
10 [1/min]
preset
ServiceTool
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
13
DI3: Increase speed
12
DI2: Decrease speed
11
System start with DI1
1)
18
Alarm
PDrv 2 Eco
Or local
Or PLC
drive