Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 33 of 48
70
80
4
D
C
B
A
5
16
17
DO
GND
16
17
DO
11
11
16
17
GND
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
2
18
+24V
DI
18
Configuration of Drive 1 (Master):
Nr.
Parameter
Change value to
Pre-settings by factory
2)
3-6-1
Type of Control
1= Discharge Pressure
3 = Differential pressure
3-11-2-1
Minimum Pressure
0.00 [bar]
-1.00 [bar]
3-11-2-2
Maximum Pressure
6.00 [bar]
6.00 [bar]
3-11-2-3
Pressure Unit
bar
Preset
1-3-2
Setpoint (Closed-loop Control)
4.00 [bar]
0,00 [bar]
3-8-2-1
Analog Input 2 Signal
2 = 2…10V
3)
0 = OFF
3-8-2-2
Analog Input 2 Function
5 = Discharge Pressure
0 = No Function
3-8-2-3
Analog Input 2 Lower Limit
0.00 [bar]
-
3-8-2-4
Analog Input 2 Upper Limit
6.00 [bar]
-
3-8-4-1
Function M12 Module Input A
2 = PMtr Internal Suction/Discharge Pres-
sure
4)
1 = PMtr Suction/Discharge Pres-
sure
3-7-1
Role in Multiple Pump System
0 = Master control
Preset
3-7-2
Maximum Number of Pumps Running
1
1
3-7-4-1
Automatic Pump Changeover
1 = Runtime
Preset
3-7-4-2
Runtime Prior to Pump Changeover
24
Preset
3-8-6-1
Digital Input 1 Function
System Start
1)
Preset
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI
1)
2
Actual value: pressure sensor 4…20mA
18
Alarm
4
Tailor-made bus cable for the connection of PumpMeter to the M12
Module (color: black, female: straight, male: angled)
5
Tailor-made bus cable for double and multi pump operation (color:
purple, male: angled, male: angled)
Nr.
Function
70
M12 Module: Double and multi pump operation
80
M12 Module: PumpMeter
A
M12 12 Module female A: connection PumpMeter (Modbus)
B
-
C
M12 Module female C: Bus resistor
D
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
Master
Or local
Or PLC
drive
O
N
O
N