Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 14 of 48
16
17
DO
GND
16
17
16
17
GND
18
+24V
DI
18
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
2
DO
11
1
1
AO: 0...10V
0...10V
0V (GND)
AO: OUT 0V(GND)
11
2.2.3
Closed loop control: differential pressure with sensor 4…20mA set point via analog input
A constant differential pressure of 4 bar is needed. The 4…20mA differential pressure sensor with a measurement range of 0-6 bar is
connected to analog input 2. The set point is given via analog input 1 by a voltage 0…10V signal. The set point is 4 bar is equivalent to
6,66V (10V/6bar*4bar).
Info: the set point via analog input has a higher priority than the set point via display.
Δp
6,66 V
1
2
Nr.
Parameter
Change value to
Pre-settings by factory
2)
Changeable by
3-6-1
Type of Control
3 = Differential Pressure
0 = OFF (Open-loop
Control)
ServiceTool, Display
3-11-2-1
Minimum Pressure
0.00 [bar]
-1,00 [bar]
ServiceTool
3-11-2-2
Maximum Pressure
6.00 [bar]
999,99 [bar]
ServiceTool
3-11-2-3
Pressure Unit
bar
preset
ServiceTool
3-8-1-1
Analog Input 1 Signal
4 = 0…10V
0 = Off
ServiceTool, Display
3-8-1-2
Analog Input 1 Function
1 = Setpoint/Control value
(Auto)
0 = No Function
ServiceTool, Display
3-8-1-3
Analog Input 1 Lower Limit
0.00 [bar]
-
ServiceTool, Display
3-8-1-4
Analog Input 1 Upper Limit
6.00 [bar]
-
ServiceTool, Display
3-8-2-1
Analog Input 2 Signal
1 = 4…20mA
0 = Off
ServiceTool, Display
3-8-2-2
Analog Input 2 Function
6 = Differential Pressure
0 = No Function
ServiceTool, Display
3-8-2-3
Analog Input 2 Lower Limit
0.00 [bar]
-
ServiceTool, Display
3-8-2-4
Analog Input 2 Upper Limit
6.00 [bar]
-
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
1) Digital Input 1 is set as at the factory as system start. If a digital input is set as system start, the parameter 1-3-1 System start is auto-
matically without function (see control point concept in operating manual)
2) Pre-settings for completely assembled pump, motor, drive
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI1
1)
2
Actual value: differential pressure sensor 4...20mA
1
Set point: 0...10V
18
Alarm
PDrv 2 Eco
Or local
Or PLC
Drive