Version 1.4
Application Guide PumpDrive 2 Eco
2016-10-20
2016-11-11 PDrv2-Eco_Application_Guide_rev_1_4.docx
Page 28 of 48
16
17
16
17
GND
DO
GND
16
17
DO
11
11
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO
+24V
GND
COM
+24V
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
GND
GND
AIN1
+24V
18
+24V
DI
18
11
70
80
4
D
C
B
A
5
3.2
Double pump – closed loop control
3.2.1
Closed loop control non redundant: differential pressure with PumpMeter (Modbus) –
typical application
Etaline Z double pump (2x100%): A constant differential pressure of 4 bar is needed. PumpMeter is used as a differential pressure sensor
in the measurement range of -1 … 10 bar. PumpMeter is connected by Modbus to the M12 Module of the drive. The set point is given by
the display. Pump changeover will take place regularly after 24 hours of operation.
Δp
4
A
D
C
5
Configuration of drive 1 (Master):
Nr.
Parameter
Change value to
Pre-settings by fac-
tory
2)
Changeable by
3-6-1
Type of Control
3 = Differential Pressure
preset
ServiceTool, Display
3-11-2-1
Minimum Pressure
-1.00 [bar]
preset
ServiceTool
3-11-2-2
Maximum Pressure
10.00 [bar]
preset
ServiceTool
3-11-2-3
Pressure Unit
bar
preset
ServiceTool
1-3-2
Setpoint (Closed-loop Control)
4.00 [bar]
preset acc. specified
Q,H
ServiceTool, Display
3-8-4-1
Function M12 Module Input A
1 = PMtr Suction/Discharge
Pressure
preset
ServiceTool, Display
3-7-1
Role in multi pump operation
0 = Master
preset
ServiceTool, Display
3-7-2
Pumps running
1
preset
ServiceTool, Display
3-7-4-1
Automatic pump change
1 = operating hours
preset
ServiceTool, Display
3-7-4-2
Time pump running
24
preset
ServiceTool, Display
3-8-6-1
Digital Input 1 Function
System Start
1)
preset
ServiceTool
Nr.
Function
16
Enable power electronic
17
Ground for digital inputs
11
System start with DI
1)
18
Alarm
4
Actual value: tailor-made bus cable for the connection of PumpMeter
to the M12 Module (color: black, female: straight, male: angled)
5
Tailor-made bus cable for double and multi pump operation (color:
purple, male: angled, male: angled)
Nr.
Function
70
M12 Module: Double and multi pump operation
80
M12 Module: PumpMeter
A
M12 Module female A: connection PumpMeter (Modbus)
B
-
C
M12 Module female C: Bus resistor
D
M12 Module female D: for Double and multi pump operation (KSB-de-
vice bus)
PDrv2 Eco
Or local
Or PLC
Drive
Master
Slave
Master
Slave
Drive 1 (Master)
Drive 2 (Slave)