MPT
700
39
4.16 Parameters 48, 54, 68, 74 - minimum on time
•
These parameters are effective in modes of operation 3, 4, 7, 8
•
Range of values: 50ms...160s (for steps, see section 4.15)
•
In case of Kromschröder burner control boxes, assuming that the main gas flow
is only released when safety delay has elapsed:
min. on time > waiting safety delay
•
For further details, see the subsections dealing with modes of operation 3, 4, 7,
8
4.17 Parameters 49, 55, 69, 75 - minimum off time
•
Range of values: 50ms...160s (for steps, see section 4.15)
•
The minimum off time must always be set.
•
The minimum off time always refers to 100 % control setting.
•
The maximum pulse frequency available can be calculated from the minimum
off time and the maximum pulse width set or the minimum on time.
Example: max. pulse width:
400 ms
min. on time:
-
min. off time:
100 ms
⇒
min. cycle time:
500 ms
⇒
max. frequency:
2 Hz
This applies to 100% control setting without continuous pulsing.
4.18 Parameters 50...53 / 56...59 / 70...73 / 76...79 - delays
•
These parameters are effective in modes of operation 5 ... 8
•
Range of values: 0.01 s...1 s
in 0.01 s steps
1.00 s...20 s in 0.10 s steps
•
For further details, see the subsections dealing with modes of operation 5 ... 8.