5.3 Brief instructions
The following paragraphs give a brief survey of the most important settings and all
parameters.
5.3.1 Modes of operation
No. Mode of operation
Section
1
Heating with fixed pulse width and variable frequency
3.1
2
Heating/cooling with fixed pulse width and variable frequency
3.2
3
Heating with variable pulse width and spacing
3.3
4
Heating/cooling with variable pulse width and spacing
3.4
5
Heating with fixed pulse width and separate air and gas valve control
3.5
6
Heating/cooling with fixed pulse width and separate air and gas valve
control
3.6
7
Heating with variable pulse width and spacing and separate air and gas
valve control
3.7
8
Heating/cooling with variable pulse width and spacing and separate air
and gas valve control
3.8
5.3.2
Parameter 10 - setting source
•
Together with the active setting source indicators (off, 1...4), this parameter
defines the source of the setting in NORMAL OPERATION and in the event of a
FAULT.
Parameter value VWD= off VWD=1
VWD=2
VWD=3/4
0 off
off
off
off
1 off
0...20
0...20
manual
2 off
4...20/off
4...20/off
manual
3 off
TPS
TPS
manual
4 off
manual
4...20/manual manual
5 off
off
off
manual
VWD: number of active setting source indicator
TPS:
3-point step controller
•
If the unit is switched to "MANUAL" or "TPS" in the event of a fault, the last valid
setting is used.