MPT 700
38
4.14 Parameter 38, 39 - fixed setting
•
This parameter is effective in modes of operation 1 ... 8
•
Range of values: 0, 1...100% in 1% steps
•
The fixed setting is used for special purposes such as reduction.
•
Depending on the signal at INPUT 1 and INPUT 2 the unit is either operated at
the setting received from the controller or at the fixed setting stored in
parameter 38, 39.
INPUT 1/3 inactive
⇒
controller setting
INPUT 1 active
⇒
fixed setting for group 1
INPUT 3 active
⇒
fixed setting for group 2
CAUTION: If the parameter is set to 0,
⇒
no fixed setting is valid even if INPUTS 1/3 are active
4.15 Parameters 40...47 / 60...67 - pulse widths
•
These parameters are effective in modes of operation 1, 2, 5, 6
•
Range of values: 50ms...160s
The pulse width can be set separately for each channel.
Range Step
0.050s...0.500s 0.005s
0.500s...1.000s 0.025s
1.000s...10.000s 0.100s
10.000s...60.000s 0.250s
60.000s...120.000s 0.500s
120.000s...160.000s 1.000s