MPT 700
32
4.2 Parameter 11 - mode of operation
Range of values: 1...8
•
The value of this parameter corresponds to the mode of operation selected (see
section 3).
4.3 Parameter 12, 13 - equipment address
•
The equipment address is not relevant for operation. Indeed, all the units can
even be set to the same number with no adverse effects on operation.
•
Range of values: 1...32
4.4 Parameter 14 - setting indicator
•
Range of values: 0...2
•
If this parameter is set to "0", the setting indicator is switched between group 1
and 2 and vice versa at intervals of 3 sec.
•
If "1" or "2" is selected, only the setting of the corresponding group is indicated.
•
This parameter is only relevant in operation with a controller. In the case of
manual input, the setting of the group currently selected is always indicated.
4.5 Parameters 15, 16 - number of outputs
•
Range of values: 0...8
•
Parameter 15 - group 1 outputs
Parameter 16 - group 2 outputs
•
The total number of outputs connected must not exceed 8. Otherwise, the
unit will signal a failure and all four setting source LEDs will flash.
•
See also section 4.6 for restrictions on the number of outputs available in mode
108.