correctly. This will be the case if there is a functional interrelationship between
the two parameters.
•
Error type C:
This error type is signaled if an error counter (parameter 90...98) overflows
and internal error handling procedures are ineffective (see section 5.4.6).
In the case of an equipment fault, the same error will be signaled within a short
time of resetting the signal.
If a cold start (see section 5.4.8) does not solve the problem, please return the
unit to one of our authorized dealers, giving an exact description of the problem
and stating the error code (parameter 9).
5.4.6
Parameters 90...98: event counters
•
The event counters indicate the number of cold starts and various internal
errors.
•
If a counter overflows (value 2048), a malfunction is signaled (see section
5.4.5).
•
The event counters may be reset to zero by pressing the bottom right button.
The counters should only be reset following an overflow.
5.4.7
Parameter 99: display test
•
It is possible to test each segment of the display by pressing the two buttons on
the right.
5.4.8 Cold start
•
Disconnect the MPT 700 from the power supply for about 10 seconds.
•
Following reconnection to the power supply, the MPT 700 is reset to its normal
status if no internal or external errors are active.
5.4.9 Connections
•
Please check all the connections using the block diagram in section 5.2.5 and
the potentials at all connections before returning the unit to one of our
authorized dealers.