MPT 700
50
Notes:
•
The blocks shown are isolated from each other.
•
The jumpers shown must be installed directly on the connector.
•
Preferably shielded cables should be used. The shield must be grounded at
both ends.
•
The loads to be switched must be connected between 6/8b and the
appropriate output.
•
Output 12z must be wired to ensure that the plant concerned is set to a safe
condition in the event of a fault.
•
For the control of contacts 14z/d...18z/d via relays, the auxiliary voltage on
2/4b and 10/12b may be used (jumper 10/12b-14/16b or 10/12b-18b, relay
contact between 2/4b and the input concerned).
•
Unused inputs must be connected to the appropriate GND contact.
•
Contacts 32z/b/d must be connected to the PE (ground) conductor (VDE
0100)!
•
Please follow the notes in section 5.1!
5.2.6 Terminal plan (CN1)
Type F
Z
B
d
2
OUT 1
+12...24 VDC
OUT 2
4
OUT 3
+12...24 VDC
OUT 4
6
OUT 5
COM OUT
OUT 6
8
OUT 7
COM OUT
OUT 8
10
OUT H/C 1
GND
OUT H/C 2
12 OUT
/ERROR GND reserved
14
IN 1 - fixed setting 1 IN1-4 GND
IN 2 - parameter set 2/1
16
IN 3 - fixed setting 2 IN1-4 GND
IN 4 - group 2/1
18
IN TPS-INCR.
TPS GND
IN TPS-DECR.
20
IN mA 1
mA GND
IN mA 2
22 Reserved
Reserved
reserved
24 Reserved
Reserved
reserved
26 Reserved
Reserved
reserved
28 N
N
N
30 L
L
L
32 PE
PE
PE