MPT 700
56
5.4.5
Parameter 9: error code
•
Note this value and always state it when returning the unit to one of our
authorized dealers.
•
The error code is displayed as a hexadecimal number. If several errors are
active, their hexadecimal codes are added.
•
An 'x' indicates that the digit concerned is not relevant for this test.
Error codes:
Value Meaning
Indicator
Error
type
0000 No
error
-
-
XX01 EEPROM programming error
malfunction red
C
XX02 ROM defective
malfunction red
C
XX04 Inadmissible
parameter input
malfunction red
B
XX08 CONFIG register incorrect
malfunction red
C
XX10 RAM test error (cold start)
malfunction red
C
XX20 I/O error (time protected bits)
malfunction red
C
XX40 Stack overrun (RAM check)
malfunction red
C
XX80 Watchdog
malfunction
red C
01XX Pilot burner 1 failure
STOP
A
02XX Pilot burner 3 failure
STOP
A
04XX Pilot burner 5 failure
STOP
A
08XX Pilot burner 7 failure
STOP
A
10XX No function
01 flashes green A
20XX < 2 mA or > 20,7 mA in 4-20 mA
operation
> 20,7mA in 0...20mA operation
'mA' 02 flashes
green / mal-
funktion LED
steady light
A
40XX Reserved
80XX Reserved
•
Error type A:
These errors are automatically reset if the cause (pilot burner failure, line break
or communication failure) is remedied by the customer.
•
Error type B:
These errors are automatically reset, if the customer sets the parameters to
values appropriate for the mode of operation.
Type B errors may for example be signaled if the mode of operation is changed
and not all the parameters are set to appropriate values.
The number of the "first incorrect parameter" is indicated by the left two digits
of parameter 8.
Please check the values of all parameters set on the basis of the parameter list
in section 3 for the mode of operation selected and the notes concerning the
parameters in section 4.
Please note that the parameter indicated as the "first incorrect parameter" may
be incorrect because another parameter with a higher number has not been set