4 Adjustable parameters 10...87
The following paragraphs give a detailed explanation of the adjustable parameters
of the unit.
Please start by selecting a mode of operation (section 3) and then set the
parameters of the MPT 700 to the values required for the mode of operation
selected.
If possible, do not change any parameters while the unit is in operation (except
using the function "parameter set 2"). Otherwise, inadmissible parameter values
may cause malfunctions.
A Complete list of all parameters is included in section 5.3.3.
4.1 Parameter 10 - setting source
•
Range of values: 0...5
•
Depending on the active setting source indicator (off, 1...4), this parameter
defines the source of the setting in NORMAL OPERATION and in the event of a
FAULT.
Parameter value VWD = off VWD = 1
VWD = 2
VWD= 3/4
0 off
off
off
Off
1 off
0...20
0...20
Manual
2 off
4...20/off
4...20/off
Manual
3 off
TPS
TPS
Manual
4 off
manual
4...20/manual Manual
5 off
off
off
Manual
VWD: number of active setting source indicator
TPS:
3-point step controller
If the unit is switched to "MANUAL" or "TPS" in the event of a fault, the last valid
setting is used
Example:
setting source 1:
mA input
setting source 2:
off
active setting source:
01
parameter 10:
2
⇒
normal operation: 4-20 mA continuous controller
mA fault:
all outputs are reset
If this controller also fails (<2mA or > 20,7mA in (4...20mA) operation as well as >
20,7mA in (0...20mA) operation), all outputs are reset.