MPT
700
29
Pulse diagram:
1. setting 1%
⇒
min. on time / max. off time
ZZP
air valve
gas valve
delay
2. setting 1%...XX%
⇒
min. on time / off time is reduced
ZZP
air valve
gas valve
delay
3. setting XX%
⇒
min. on time / min. off time maximum pulse
frequency
ZZP
air valve
gas valve
delay
4. setting XX%...99%
⇒
min. off time / on time is increased
ZZP
delay
air valve
gas valve
5. setting 100%
⇒
continuous pulse
gas valve
air valve
XX%
⇒
value in parameter 28 (10...90%)