MPT
700
37
Example: dead zone = 10% / H/C limit = 50%
0...20mA controller: 10% of 20mA
⇒
dead zone = 2mA
⇒
0mA...9mA
⇒
cooling
9mA...11mA
⇒
dead zone
11mA...20mA
⇒
heating
4...20mA controller: 10% of 16mA
⇒
dead zone = 1.6mA
⇒
4.0mA...11.2mA
⇒
cooling
11.2mA...12.8mA
⇒
dead zone
12.8mA...20.0mA
⇒
heating
4.12 Parameter 34, 35 - continuous pulse
•
Range of values: 0, 50...100% in 1% steps
•
Value = 0
⇒
no continuous pulse
i.e. at 100% control setting, the unit operates at maximum frequency without
switching to continuous pulse.
•
Value = 50...100% (from the value entered, all outputs are set to continuous
pulse)
4.13 Parameter 36, 37 - control rate (three-point step controller)
•
Range of values: 1...180s in 1s steps
•
The control rate indicates the time taken for changing the signal from 0 to
100%.
Example: control rate = 30s
current setting = 50%
signal three-point step controller = OPEN
⇒
time required from 50...100% = 15s