From the measured differential pressure and the follo-
wing formula, the current air flow can be calculated (for
an air temperature of 20°C).
In case of multi-fan units, the stub is connected to one
of the fans.
Qv=n
w
k√(Δp
w
)
Qv - airflow rate [m3/h]
n
w
- number of fans in the set
k - characteristic coefficient for the fan
nozzle
Δp
w
- static pressure drop on the fan nozzle [Pa]
Fig. 72
Differential pressure measurement scheme on the fan orifice
Table 20
K-factors for ZIEHL-ABEGG and EBM-PAPST fan nozzles
Fan type
K-factor
Fan type
K-factor
RH22C
47
R3G250RR01-H1
68
RH25C
60
R3G280-PR04-I1
77
RH28C
75
R3G310-AX54-21
116
RH31C
95
R3G355-AY43-21
148
RH35C
121
R3G400-PI92-01
188
RH40C
154
R3G450-PB24-01
240
RH45C
197
R3G500-PB33-01
281
RH50C
252
K3G630-PW04-01
438
RH56C
308
K3G710-PW06-01
545
RH63C
381
R3G250-PR17-I1
76
RH71C
490
R3G280-PS10-J1
77
R3G310-BB49-01
116
R3G355-PI93-01
148
R3G355-BC92-01
148
R3G400-AQ23-68
188
GR25C-6ID.BD.CR
60
GR31C-ZID.DC.CR
95
GR35C-ZID.DC.CR
121
4.10 UVC-S lamp
UVC-S lamps are designed to irradiation of the surfaces of
selected structural elements and devices installed inside
the unit
They are used in the cooling and filtration sections to irra-
diate:
• the surface of the lamellas of the coils from the air inlet side
and partly the condensate drip tray,
• filter inlet surface (dirty part).
Micro-suicidal protection is ensured by the use of high-per-
formance radiants producing in the light spectrum, a UVC
wavelength of approximately 254 nm. The radiant lumina-
ires are equipped with reflector-directing reflectors, which
increases their action. Lamp casing provide IP55 protection.
Most bacteria, mold and viruses are deactivated by long-
term UVC rays. The formation of biofilm on their surfaces is
significantly reduced, which shortens the chemical washing
process.
Inspection windows are additionally equipped with a filter
against the ingress of UVC light harmful to the eyes and
skin. Despite the filter used, however, it is not recommen-
ded to observe the space inside the UVC section for a long
time.
4.10.1 UVC-S lamp connection
UVC-S lamps must be electrically connected according to
the scheme. The lamps are powered by a single-phase vol-
tage of 230V / 50 Hz.
4.10.2 UVC-S lamp maintenance
Check the condition of the lamps periodically.
Maintaining cleanliness is important because its bacteri-
cidal effect may not be sufficient to carry out disinfection.
If the UVC lamp fluorescent lamp or the light reflecting lamp
casing becomes dirty, clean it with a clean alcohol-stained
cloth, avoiding touching the glass parts with your hands.
The total operating time of UVC-S lamps is counted by the
automation system. After working the right number of ho-
urs, will appear the information about need to replace the
fluorescent lamps and will display an alarm signal.
UVC light for sterilization is not visible to human vision, so
it is not possible to determine the correctness of its action
by observation.
It is recommended that the replacement of UVC-S fluore-
scent lamps be carried out by an authorized KLIMOR service
center.
All components exposed to irradiation from
UVC lamps must be made of UVC-resistant
materials
Summary of Contents for EVO - H
Page 60: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Page 118: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Page 119: ...EVO S EVO H KLIMOR...
Page 127: ...125 14 11 12 13 3 2 15 16 15 16 17 17 18 18 RR OMM KL RR ASM GUILS Klimor...
Page 130: ...128 EVO S EVO H 25 26 c 200x200 300x200 27 27 d 0230 0090 300x200 28 28 0230 0090...
Page 132: ...130 EVO S EVO H 2900 a 50 31 b 150 32 c 33 2900 b c...
Page 141: ...139 43 8 1200 600 230 50 36 310 x 230 x 125 4 3 2 E G4 ISO COARSE 60 6...
Page 142: ...140 EVO S EVO H 44 45 46 100 C 47 48 49...
Page 143: ...141 4 3 3 SR 50 230 50 60 CA 1 2 CG 3 2 CG 3 1 CA 4 3 4 52 51...
Page 144: ...142 EVO S EVO H 53 54 55 4...
Page 145: ...143 56 4 3 5 G4 ISO COARSE 60 6 57 57 58 INOX 2 3 Power supply LED C 3x2 5 2x2 5 C 2x1 5...
Page 146: ...144 EVO S EVO H 59 60 C 4 4 WH CuAl 4 8 1 4 5 EH 60 4 5 1 4...
Page 149: ...147 62 3 5 4 5 6 7 63 8 4 9 64 63 64 4 7 2 12 5 5...
Page 157: ...155 150 4 12 1 CPR PR 6 12 50 0 C 4 13 RG 55 76 Cu Al Cu Al 23 DN63 PN Klimor Klimor 230 50...
Page 167: ...165 4 14 2 3 4 14 3 Klimor 5 6 6 1 KT 8 100 C...
Page 168: ...166 EVO S EVO H 7 12 PN EN 13779 2008 12 2000 24 4000 24 4000 3 6 12 30 C 130 C 4...
Page 169: ...167 8 30 1 2 3 DX 4 5 6 7...
Page 171: ...169 10 KLIMOR EVO KLIMOR EVO a b 10 10 c IP54 d c e 83 84 f IP65 85 86 32 A 50 0 1 1...
Page 173: ...171 11 7 11 8 11 9 91 11 10 DIN 1946 4 DIN 1946 4 DIN 1946 4 DIN 1946 4 3 I 2 4 0 8 80 20 1...
Page 174: ...172 EVO S EVO H 11 11 m in HEPA...
Page 175: ...173 m in HEPA EN ISO 14644 1 3...
Page 176: ...174 EVO S EVO H 12...
Page 177: ......