“PHO2” OPENING OR OPENING/CLOSING PHASE SAFETY DEVICES
It is possible to connect devices (e.g. photocells or edges) with nor-
mally closed (NC) contact to the “
PHO2
” input (terminal 6-7).
The factory wire bridge connected to PHO2 must be removed when
using this input.
These devices intervene while the gate is moving, according to the
setting of DIP5 (see par. 3.1).
DIP5 set to ON (operation as photocells)::
- in
closing phase
they continue the movement as soon the device
has been cleared
- in
opening phase
they continue the movement as soon the de-
vice has been cleared
- if the
access is closed
they inhibit the opening commands.
- if the
access is open
they inhibit the closing commands.
DIP5 set to OFF (operation as opening edge):
- during the
closing phase
they have no effect
- during the
opening phase
they re-close the gate fully
- with the
gate closed
they lock the opening commands.
- with the
gate open
they have no effect.
Figures 11a, 11b and 11c show examples of King Gates “Viky30”
photocell connections.
When multiple devices are connected on this contact, they
must be series connected (see Fig. 11c).
If more photocell pairs are connected, RX and TX units of
the safety set should be cross installed (see Fig. 11c).
+VA (8)
GND (7)
1 2
+VA (8)
GND (7)
PH01 (5) o
PH02 (6)
1 2 3 4 5
RX1
TX1
TX2
RX2
1 2 3 4 5
1 2 3 4 5
+VA (8)
GND (7)
PH01 (5) o
PH02 (6)
+VA (8)
GND (7)
GND (7)
The numbers refer to the paragraphs below
corresponding to the terminals
11
See Paragraph 2.4
See Paragraph 2.4
Connection of the
TX transmitter
11a
Connection
of RX receiver
Viky30
11b
See Paragraph 2.4
Connection of multiple
receiver pairs
Viky30
Receiver
pair 1
Transmitter
pair 1
Transmitter
pair 2
Receiver
pair 2
11c