30
3. Installation
3.1 Installation example: KESSEL Oil / Fuel Separator
Illustration shows KESSEL-oil-/fuel separator class II with cover class B and sampling chamber.
3.2 Dimensioned drawing
h2
T
L max.
h1
B
DN/OD
DN/OD
L
TEÜ**
OKB
DN 150: T-T
EÜ
= 155 mm
DN 200: T-T
EÜ
= 180 mm
T-T
EÜ
= Height above ground
Class D: 700 mm ≤ T
EÜ
≤ 1.500 mm
Class A/B: 700 mm ≤ T
EÜ
≤ 1.800 mm
DN
150
200
200
150
200
200
200
200
B
1200
1760
1760
1200
1760
1760
1760
1760
max
124
0
1230
1250
1240
1230
1250
1250
1250
h2
1100
1630
1630
1100
1630
1630
1630
1630
h1
1070
1600
1600
1070
1600
1600
1600
1600
L
2390
2590
3110
2910
2590
3110
3110
3110
Sludge trap
1000 l
2500 l
5000 l
1500 l
2500 l
5000 l
5000 l
4000 l
Oil storage
215 l
380 l
470 l
267 l
380 l
470 l
470 l
470 l
Overhang
90 mm
120 mm
130 mm
100 mm
120 mm
130 mm
130 mm
130 mm
Weight
379 kg
519 kg
594 kg
424 kg
519 kg
594 kg
594 kg
600 kg
L
max
mm
2642
2940
3460
3162
2940
3460
3460
3460
NS
NS 3
NS 6
NS 6
NS 10
NS 10
NS 10
NS 15
NS 20
min
840
850
870
840
850
870
870
870
T
1)
1)
2)
2)
2)
2)
1) Comparable total sludge trap volume according to dimensioning of DIN EN 858
2) Eccentric reduction of inlet/outlet to DN 150 possible on site, fitted through DN 150 sample removal shaft
1800
4300
5800
2600
4300
5800
5800
5800
Total
volume
Summary of Contents for 99403.10B