Maintenance
77 / 264
03/2015
6.2.1 6.2.1 Maintenance card
Inspection/maintenance Ecolift XL
Please note the safety instructions
Building description
Building
Street
Postcode, city
Contact
System variant
Mono
❏
Duo
❏
Serial number
Pump type
1
❏
2
❏
Inspection: Once a month by the operator:
No.
Test
Done record
yes no
1
Check the display of control unit 1 Comfort Plus for possible fault messages
2
Manual function test on Comfort Plus and on control unit for redundant valve if present,
close flap A (sewer side) (using flap test hand symbol)
Make sure of inflow (clear water)
➞
wait to see if the pump starts working
3
Manual function test on control unit for redundant valve if present
close flap B (house side) (using flap test hand symbol)
Make sure of inflow (clear water)
➞
wait to see if the pump starts working
A rising level can be seen on the display. Inlet until switch-on point 1 or switch-on point 2 has been reached, then
pump operation starts.
“On” level: ______________________
“Off” level: ______________________
Since pumps 1 and 2 pump alternately, always wait two operating cycles.
4
Test compressor set
➞
listen to check whether the compressor is running. Use manual
pump to free hose of condensation
5
If pump is pumping
➞
stop inflow
6
Open the flap of the control unit redundant flap again manually, then
7
Open the flap of the Comfort Plus control unit again
If a fault message appears, proceed according to the control unit instructions.
Maintenance: by a maintenance expert in accordance with the maintenance interval:
8
Steps 1-7 must be carried out as described above.
9
Open the inspection chamber and check the cover seal for damage
10
Carry out a visual inspection of the upper section and visual inspection of the inspection
chamber and the control cable
11
Disconnect the system from the mains and secure it against being switched on again
Summary of Contents for 010-694
Page 42: ...42 264 Leistungserkl rung DOP 03 2015 9 Leistungserkl rung DOP...
Page 43: ...Leistungserkl rung DOP 43 264 03 2015...
Page 86: ...86 264 Declaration of conformity 03 2015 9 Declaration of conformity...
Page 87: ...Declaration of conformity 87 264 03 2015...
Page 129: ...D claration de conformit 129 264 03 2015 9 D claration de conformit...
Page 130: ...130 264 03 2015...
Page 131: ...131 264 03 2015...
Page 173: ...Dichiarazione di conformit 173 264 03 2015 9 Dichiarazione di conformit...
Page 174: ...174 264 Dichiarazione di conformit 03 2015...
Page 175: ...175 264 03 2015...
Page 218: ...218 264 Conformiteitsverklaring 03 2015 9 Conformiteitsverklaring...
Page 219: ...Conformiteitsverklaring 219 44 03 2015...
Page 261: ...Dane techniczne 261 264 03 2015...
Page 262: ...262 264 Deklaracja zgodno ci 03 2015 9 Deklaracja zgodno ci...