76 / 264
Maintenance
03/2015
6
Maintenance
Before housing covers, plugs and cables (including those on potential-free contacts) are opened they must be
switched voltage-free. Work on electrical components may only be carried out by specialist staff (see 2.2).
6.1
General maintenance information
No climbing on electrical components, pipe connections or cables during maintenance work.
Risk caused by toxic and hazardous vapours, gases and substances (e. g. bacteria, viruses). If the backwater
lifting station is located in an inspection chamber, any necessary work must always be done by specialist staff
(see 2.2).
Risk of drowning in the system chamber. In the event of a flood, a system chamber can fill with water within a
very short time. If there is a risk of water entering, the chamber must not be entered until there is no danger
involved.
After all maintenance work, carry out a function test on the backwater lifting station (see 6.2.1).
6.2
Maintenance intervals
The maintenance date can be set in the menu 2. Maintenance / 2.4 Maintenance date (see control unit
instructions). When the maintenance date has arrived, this will be indicated by a plain text message on the
display.
Maintenance of lifting stations
The backwater lifting station must be maintained regularly by an appropriate expert. The intervals must not
exceed:
- 6 months for systems in commercial use
- 1 year for systems in private use
A maintenance protocol with details of all the work carried out and the main data must be prepared for all
maintenance work.
In as far as faults are found which cannot be eliminated, the system operator must be notified immediately in
writing by the maintenance expert, and must confirm receipt of this notification.
Summary of Contents for 010-694
Page 42: ...42 264 Leistungserkl rung DOP 03 2015 9 Leistungserkl rung DOP...
Page 43: ...Leistungserkl rung DOP 43 264 03 2015...
Page 86: ...86 264 Declaration of conformity 03 2015 9 Declaration of conformity...
Page 87: ...Declaration of conformity 87 264 03 2015...
Page 129: ...D claration de conformit 129 264 03 2015 9 D claration de conformit...
Page 130: ...130 264 03 2015...
Page 131: ...131 264 03 2015...
Page 173: ...Dichiarazione di conformit 173 264 03 2015 9 Dichiarazione di conformit...
Page 174: ...174 264 Dichiarazione di conformit 03 2015...
Page 175: ...175 264 03 2015...
Page 218: ...218 264 Conformiteitsverklaring 03 2015 9 Conformiteitsverklaring...
Page 219: ...Conformiteitsverklaring 219 44 03 2015...
Page 261: ...Dane techniczne 261 264 03 2015...
Page 262: ...262 264 Deklaracja zgodno ci 03 2015 9 Deklaracja zgodno ci...