Aufstellung.pm6.5 - GB
Page 3.4
Installation
BOGE Operating instructions for CM 9 series screw compressor module
Condensate disposal
3.2
Compressor room
Please refer to the following table for the cooling air requirement and size of
the supply air openings for your compressor. Ensure that flaps and weather
protection grids have the necessary free cross section. We generally recom-
mend contacting a specialist company for performing the duct construction
work and planning.
Cooling
air requirement
(with air cooling)
Type
Drive
* Cooling air
Necessary
rating
requirement
inlet opening
for free
for free
standing unit
standing unit
[kW]
[m
3
/h]
[m
2
]
CM 9
2.2 – 7.5
800 – 2800
0.10 – 0.35
Table 1: cooling air requirement, necessary
aperture dimensions.
* For the cooling air requirements the basis is a 4° C temperature difference between room
and outside temperature.
The air taken in contains water in form of vapour, which turns into conden-
sation during compression.
ATTENTION!
The condensate contains oil. Never lead it into the public sewage system
without prior treatment.
Strictly observe the effluent disposal laws of your local authorities.
Oil-water-seperator
The
BOGE-oil-water-seperator
(available as accessories) separates the oil
from the condensate.
The cleaned water may be fed directly into the public sewage system.
The oil is collected in a separate container. Dispose of the oil according to
environmental regulations.
If, due to special operating conditions, the oil should emulsify, use an emul-
sion cracking plant.
Summary of Contents for BOGE CM9 Series
Page 1: ...Deutsch English Fran ais Italiano Espa ol Nederlands 5 963 387 0 08 09 BOGE CM9...
Page 2: ......
Page 3: ...Betriebsanleitung Schraubenkompressor Modul Baureihe CM 9...
Page 46: ...Operating instructions Screw compressor module Serie CM 9...
Page 89: ...Instructions de service Module pour compresseurs vis S rie CM 9...
Page 134: ...Modulo Compressore a vite Serie CM 9 Istruzioni per l uso...
Page 177: ...Instrucciones de uso Compresores de tornillo M dulo Serie constructiva CM 9...
Page 220: ...Bedrijfsvoorschrift Schroefcompressor module Serie CM 9...
Page 263: ......