49
Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
DIP switch no. 1
DIP switch no. 1 must be set to ON to actuate a KaControl by means of
0…10 V signals within a building management system provided by others.
The parameter settings required are described in Section 10.3.17.
Factory setting:
DIP1 = OFF
DIP switch no. 2
It is essential that DIP switch no. 2 is set to OFF.
Factory setting: DIP2 = OFF
DIP switch no. 3
A frost protection sensor can be connected to provide frost protection. In
this case, DIP switch no. 3 must be set to ON.
Factory setting: DIP3 = OFF
DIP switch no. 4
Summer mode / winter mode changeover is set as standard using the
KaController. Alternatively, summer mode / winter mode changeover can
also be performed by an external thermostat or an external switching
contact.
In this case, DIP switch no. 4 must be set to ON.
DIP4 = ON + external thermostat contact open
Winter mode
DIP4 = ON + external thermostat contact closed
Summer mode
DIP4 = OFF (no external thermostat fitted)
Factory setting: DIP4 = OFF
DIP switch no. 5
It is essential that DIP switch no. 5 is set to OFF.
Factory setting: DIP5 = OFF
DIP switch no. 6
There is an option of using the internal sensor in the KaController or an
external room temperature sensor for temperature control.
DIP-Schalter Nr. 6 = OFF room temperature control on a suction / external
room sensor
DIP-Schalter Nr. 6 = ON room temperature control on the internal sensor
of the KaController
Factory setting: DIP6 = ON