Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
Parameter P44
Parameter P44 is used to set the function of the digital input DI2 when DIP
switch no. 4 = OFF.
Parameter P56
The polarity of digital input DI2 is set using parameter P56 when setting DIP
switch no. 4 to ON.
The digital input DI1 is predominantly used to execute specific functions. If
the use of the digital input DI2 is needed, then the following settings must
be made:
1. Set DIP switch no. 4 to OFF.
2. Configuration of the digital input DI2 using parameter settings P44
10.12.3 DI2 function
Position
Standar
d
Min
Max
Unit
P44
P44 function DI2
0 = no function
1 = ON/OFF
(contact open ON)
2 = winter/summer changeover
(contact open heating)
3 = Eco/Day mode
(contact open Day)
4 = no function
(contact open without function)
5 = condensation alarm
(contact open no condensation)
6 = general alarm
(contact open no alarm)
7 = external Frost protection monitor (contact open no frost)
8 = ON/OFF
(contact closed ON)
9 = winter/summer changeover
(contact closed heating)
10 = Eco/Day mode
(contact closed Day)
11 = no function
(contact closed no function)
12 = condensation alarm
(contact closed no condensation)
13 = general alarm
(contact closed no alarm)
14 = external frost protection monitor (contact closed no frost)
0
0
14
Position
Standard
Min
Max
Unit
P56
P56 Polarity of DI2 if DIP4 = ON (Winter / Summer via DI2)
0 = Contact closed
winter
Contact open
summer
1 = Contact open
winter
Contact closed
summer
1
0
2
If DIP switch no. 4 is set to ON, digital input DI2 changes from winter to
summer in a 2-pipe system.