6.2 Installation of remote sensor for outlet air temperature limit valve
Proceed as follows when installing the remote
sensor:
Open the service hatch (1) on the left side of
the unit, as described in chapter 9
Fix the pipe clip (2) using the screws provided
Remove the rectifier (3) on the left side of the
unit
Carefully route the remote sensor (4) through
the opening in the outer wall (5) and the fan
bracket (6)
Press the remote sensor (4) carefully into the
pipe clip (2)
Caution!
When fitting the remote sensor, make sure that the
capillary tube does not become seriously kinked or
damaged, as the correct operation of the actuator
cannot be guaranteed in the event of damage.
2
2
1
1
1
4
4
6
5
3
An outlet air temperature limit valve is
mandatory with outlet air temperatures
of more than 40°C.