Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
10.2 UniLine AC, model for on-site control (*P)
Electrical wiring |
UniLine AC, model for on-site control (*P)
Description of switches
The mains voltage is wired to the voltage supply terminals on the door
air curtain.
The speed signal is wired to the input terminals on the door air curtain.
The required speed can be set by an active 0-10 VDC signal
or a 0-100 kOhm potentiometer, depending on the unit configuration.
The internal control converts the continuously variable control signal
automatically into five fan stages
Activation is possible by a release contact.
The heating valve (if fitted) can be opened or closed by an on-site
potential-free switch contact.
A possible fault message can be called up by an internal potential-free
switch contact (loadable 60 VAC, 1 A).
When switching between the fan stages, the power contactor
temporarily disables the fans to avoid transverse voltage of the
transformer.
Dip switch setting on the PCB:
Technical details for inputs/outputs on the PCB
Input impedance AE:
≥ 50 kΩ
Fault signal contact:
U = Max. 60 VAC/DC
I = Max. 1 A
Fault signal output:
U = Max. 24 VDC
I = Max. 0,5 A
LED messages on the PCB:
Continuously lit
Standby
Slow flashing 2 second-cycle
Activated
Fast flashing 0.5 second-cycle
Fault
Troubleshooting
In the event of a possible fault of the AC fans, the control shuts down in a
locked status.
After rectifying the cause of the fault, the door air curtain can be switched
on again by resetting the supply voltage.
DIP
Factory
setting
Position
Description
1
OFF
Speed signal
OFF: active 0-10 V signal
ON: Potentiometer 0-100 kΩ
2
OFF
Activation signal
OFF: Activation internally set
ON: Activation via pot.-free (external) N/O
3
ON
Program selection
OFF: Program for *C1 control
ON: Program for *P control
4
OFF
Program selection
OFF: Mandatory
Feed line
Control signal
0-10V
Fault message