Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, electromechanical model
with internal fault signal processing (*00)
10.3 UniLine EC, electromechanical model with internal fault signal processing (*00)
Description of switches
The mains voltage is wired to the voltage supply terminals on the door
air curtain.
Continuously variable speed control via an active 0…10 VDC signal.
Internal evaluation of a possible motor fault and EC fans switched off.
The heating valve (if fitted) can be opened or closed by the compact
controller type 30158 or an on-site switch command.
Compact controller
Combination of operating mode selector switch and speed sensor with
options for external control and operation.
The required room temperature is set on the compact controller.
The door air curtain is disabled in standby mode. A frost protection function
can be activated by means of settings. In winter mode the fan speed can be
set by the dial and the actuator is open. In summer mode the fan speed can
be set by the dial and the actuator is closed.
The fan can be allowed to run on or increase the speed by connecting a
door contact switch and corresponding parametrisation. Additionally, a
room temperature control can be activated, which closes the hot water
valve and disables the fan when the set temperature is reached.
Compact controller in a flat surface-mounted housing, white
Rating IP 30, voltage 230 V/50 Hz
Dimensions W x H x D: 110 x 110 x 27 mm
Feed line
Control signal
Valve drive
Valve drive