Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Maintenance |
Filters, fans and heat exchanger
Maintenance
9
Fans and heat exchanger
Caution!
Read the safety information in these instructions before working on the fans
and heat exchangers!
Maintain the maintenance intervals prescribed by legislation. Interim
maintenance depends on the general conditions on site. Only clean heat
exchangers guarantee their full heat output in the long term.
Maintenance interval: at least every 6 months or more regularly,
depending on dirt and dust levels.
Open the inspection hatch (1) by using a screwdriver to loosen the
screws (2) and carefully open the service hatch downwards.
Carefully clean the heat exchanger with a vacuum cleaner. Avoid
damaging the pipes and fins.
Repair work on the fan and heat exchanger can be carried out with the
service hatch open. Please refer to the safety information given in
point 2.
1
1
2
2
Filter
The heat output of the unit will be reduced with dirty filters and the fans
can be damaged by overloading. Regularly check the intake filters.
Check the intake filters at least 2 x annually and clean if necessary.
Check and clean the intake filter more regularly depending on the level
of dust in the ambient air.
Open the service hatch (1) as follows to monitor and check the service
hatch on the underside of the filter.
Loosen the fixing wire (3) to remove the filter fabric (4) from the air
intake grille.
If the filter is dirty, vacuum the filter fabric or wash it out.
Replace the filter in the event of serious dirt!
After cleaning/replacement, fit in the reverse order.
Caution!
Never operate the UniLine door air curtain without a filter!