Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
The function of the digital output V1 is permanently assigned. The function
of the digital output V2 can be configured using parameters.
Digital output V2
The digital output V2 is used to control the heating valve in a 4-pipe system.
The digital output V2 can be configured using parameter P39.
10.12.4 Function of digital outputs V1 and V2
Position
Standard
Min
Max
Unit
P39
P39 V2 function in a 2-pipe system
0 = no function
1 = heating requirement
2 = cooling requirement
3 = unit alarm
0
0
3
24 V DC is connected to digital output V2. The digital output is
not a potential-free contact and can only be used with
appropriate wiring!