Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
10.8 Cabling
10.8.1 General information
Route all low voltage cables along the shortest route.
Ensure that low-voltage and high-voltage cables are separated, using
metal partitions in cable ducts.
Use only shielded cables as low-voltage and bus cables.
Lay all BUS cables in a linear pattern. Star-shaped wiring is not permitted
(Figure on left).
The KaController is connected via a bus connection to the respective
control PCB on the unit.
Use shielded, paired cables as BUS cables, for instance CAT5 (AWG 18), and
at least of the same value.
When laying bus cables, avoid the formation of star points, for instance in
junction boxes. Pass the cables through to the units!
Wrong!
Star-shaped wiring of the bus lines
Correct!
Linear wiring of the bus lines
A flush-mounted back box is required for the KaController.
Connect the KaController to the nearest KaControl as per the wiring
diagram. The maximum bus length between the KaController and the
KaControl unit is 30 m.
Connecting a KaController to it automatically converts the respective
KaControl into the master unit in the control circuit.
10.8.2 KaController
** Lay shielded, paired
cables, e.g. CAT5
(AWG23) of at least the
same value, separately
from high-voltage
cables.
Mains
230V/50 Hz
Mains
230V/50 Hz
3
2**
3**
2**
3
Master
unit
#1
Flush-mounted back box
Slave unit
#2
Bus connection 30 m
Maximum length